Awaiting Analysis
This vulnerability is currently awaiting analysis. DescriptionHoneywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability. Severity
CVSS 3.x Severity and Metrics:
NVD Analysts use publicly available information to associate vector strings and CVSS scores. We also display any CVSS information provided within the CVE List from the CNA. Note: NVD Analysts have not published a CVSS score for this CVE at this time. NVD Analysts use publicly available information at the time of analysis to associate CVSS vector strings. References to Advisories, Solutions, and ToolsBy selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to nvd@nist.gov.
Weakness Enumeration
|
2023-10-27
2022-08-15
2022-08-17
2022-09-23
2022-08-13
请发表评论